Refrigeration and HVAC: Vapor Compression, Load, and Systems
What You'll Learn
- 1Analyse a vapor-compression cycle from enthalpy data and compute COP
- 2Separate sensible and latent cooling loads and size for peak with diversity
- 3Explain how lift, superheat, and subcooling change capacity and efficiency
- 4Select chillers, split systems, and terminal equipment for a building type
- 5Tune part-load control and verify performance through commissioning
HVAC keeps people, products, and processes inside narrow bands of temperature, humidity, and air quality, and refrigeration moves heat against its natural gradient by putting work into a circulating fluid. Designers size the loads, choose the cycle and equipment, distribute energy through air or water, and â most importantly of all â control the system at part load, because a machine that runs at 100 percent for a few hours a year is paid for by the thousands of hours it runs at 30 percent.
The economics follow thermodynamics directly. Every kelvin of unnecessary lift raises compressor work, every dirty coil widens the lift further, and every throttle valve in front of a fan wastes power that a variable-speed drive would have saved. This lesson builds the cycle analysis first, then the load calculations that determine size, then the distribution and control systems that decide whether the installed capacity is ever used efficiently.
The Vapor Compression Cycle and Its State Points
A vapor-compression system has four components doing four jobs. The evaporator lets low-pressure liquid refrigerant boil at a low temperature and absorb heat from the space or water being cooled. The compressor raises the suction vapor to a pressure whose saturation temperature sits above the outdoor (or cooling water) temperature so the heat can be rejected. The condenser desuperheats, condenses, and subcools that high-pressure vapor. The expansion device throttles the liquid to evaporator pressure, flashing part of it into vapor and cooling the remainder to the evaporating temperature.
Because the throttling process is isenthalpic, the enthalpy entering the evaporator equals the enthalpy leaving the condenser. The cycle analysis therefore reduces to four enthalpies on a pressure-enthalpy diagram: compressor inlet , compressor discharge , condenser outlet , and evaporator inlet . Cooling effect, compressor work, and heat rejection are then
with from the first law. Performance is
The Carnot limit for the same temperature reservoirs, with absolute temperatures, is never reached: real compressors have isentropic efficiency (0.65 to 0.80 for scrolls, 0.75 to 0.88 for screws and centrifugals), heat exchangers need a finite temperature approach, and pressure drops in valves and piping steal lift.
Two properties of the refrigerant state deserve particular attention. Superheat at the compressor inlet guarantees dry vapor so no liquid slugs the cylinder or washes lubricant out of the scroll pockets; 5 to 8 kelvin at the evaporator outlet is typical, with the expansion valve controlling it. Subcooling at the condenser outlet guarantees liquid at the expansion device; every kelvin of subcooling adds liquid enthalpy margin and roughly 0.5 to 1 percent of capacity for common HFC refrigerants, with no extra compressor work.
Worked Example 1 â Cycle COP, Capacity, and Carnot Comparison
A chiller handles refrigerant states measured as kJ/kg at compressor inlet, kJ/kg at discharge, kJ/kg at condenser outlet, and evaporating temperature 5 degrees Celsius with condensing at 35 degrees Celsius. Required cooling capacity is 35 kW.
- Cooling effect: kJ/kg.
- Compressor work: kJ/kg.
- Heat rejection: kJ/kg, and kJ/kg checks the energy balance.
- Coefficient of performance: .
- Mass flow: kg/s.
- Compressor power: kW; condenser duty kW.
- Carnot COP: , so second-law efficiency is percent.
- Chiller efficiency in industry units: kW per kilowatt, or 0.73 kW per ton of refrigeration (1 ton is 3.517 kW of cooling).
Final answer: COP 4.85, compressor 7.23 kW, condenser 42.3 kW, second-law efficiency 52 percent.
Isentropic efficiency follows from the same numbers: if the ideal discharge enthalpy were 425 kJ/kg, then percent. Anything that raises discharge pressure or lowers suction pressure â fouled condenser, dirty evaporator, refrigerant undercharge â reduces and raises simultaneously, so efficiency falls from two directions at once.
The cycle arithmetic is four subtractions plus two ratios, which makes it easy to sweep lift or enthalpy assumptions before committing to equipment:
def cycle(h1, h2, h3, cap_kW=None):
"""Cooling effect, work, COP, Carnot COP, and optional mass flow."""
qL, w, qH = h1 - h3, h2 - h1, h2 - h3
COP = qL / w
out = {"qL": qL, "w": w, "qH": qH, "COP": COP, "balance": abs(qH - qL - w)}
if cap_kW is not None:
m_dot = cap_kW / qL
out["m_dot"] = m_dot
out["P_comp"] = m_dot * w
out["Q_cond"] = m_dot * qH
return out
def cop_carnot(TL, TH):
return TL / (TH - TL)
base = cycle(400.0, 433.0, 240.0, cap_kW=35.0)
print(f"qL = {base['qL']:.0f}, w = {base['w']:.0f}, COP = {base['COP']:.2f}")
print(f"balance check (should be 0): {base['balance']:.2f} kJ/kg")
print(f"m_dot = {base['m_dot']:.3f} kg/s, P_comp = {base['P_comp']:.2f} kW")
carnot = cop_carnot(278.15, 308.15)
print(f"Carnot COP = {carnot:.2f}, second-law efficiency "
f"{100 * base['COP'] / carnot:.0f} percent")
# Fouled condenser: same evaporator, discharge enthalpy raised 6 kJ/kg.
foul = cycle(400.0, 439.0, 246.0, cap_kW=35.0)
print(f"fouled: COP {foul['COP']:.2f}, P_comp {foul['P_comp']:.2f} kW "
f"({100 * (foul['P_comp'] / base['P_comp'] - 1):.1f} percent more power)")
It reproduces the worked COP of 4.85, the 7.23 kW compressor draw, and the 52 percent second-law figure. The final lines show the fouling penalty the worked example describes qualitatively: lifting both the discharge and condenser-outlet enthalpies by 6 kJ/kg drops COP from 4.85 to 3.95 and pushes compressor power up about 23 percent for the same 35 kW of cooling â the two-direction efficiency collapse in concrete numbers.
Reading the pressure-enthalpy diagram
- Horizontal axis is specific enthalpy, vertical axis is pressure â so vertical drops across valves are isenthalpic by construction.
- The dome separates subcooled liquid (left), two-phase mixture (under the dome), and superheated vapour (right).
- Constant-temperature lines are flat inside the dome, which is why evaporation and condensation happen at constant temperature.
- Isentropic lines slope upward and to the right; the gap between them at the discharge pressure is the compressor work penalty.
- Superheat moves state points right of the dome at evaporator pressure; subcooling moves them left of the dome at condenser pressure.
- Cycle area on a temperature-entropy diagram equals the net work, and the enclosed area grows directly with lift.
Refrigerants, Regulation, and Safety
Refrigerant selection balances thermodynamic capacity, operating pressures, toxicity, flammability, and environmental impact. Ozone-depleting substances are controlled under the Montreal Protocol: R-22 (an HCFC with ODP 0.055) is being phased down in developed markets, and R-502 with it. The Kigali Amendment to the Montreal Protocol now drives a phasedown of high-global-warming HFCs, so selection increasingly follows GWP as well as performance.
| Refrigerant | Type | ODP | GWP (AR4) | Safety class | Typical service |
|---|---|---|---|---|---|
| R-134a | HFC pure | 0 | 1430 | A1 | Chillers, automotive, medium temperature |
| R-410A | HFC blend R-32 and R-125 | 0 | 2088 | A1 | Residential and light commercial AC |
| R-404A | HFC blend | 0 | 3922 | A1 | Commercial refrigeration, being replaced |
| R-32 | HFC pure | 0 | 675 | A2L | New AC and heat pump systems |
| R-290 | Hydrocarbon propane | 0 | 3 | A3 | Small AC, commercial racks, chillers |
| R-717 | Ammonia | 0 | 0 | B2L | Industrial refrigeration, cold storage |
| R-744 | Carbon dioxide | 0 | 1 | A1 | Transcritical commercial, heat pumps |
| R-1234ze | HFO | 0 | 7 | A2L | Low-pressure chillers, process cooling |
| R-22 | HCFC | 0.055 | 1820 | A1 | Legacy equipment, being replaced |
Safety classes (A means low toxicity, B higher toxicity; 1 nonflammable, 2L mildly flammable, 2 flammable, 3 flammable) come from ISO 5149 and ASHRAE 15 and they drive machinery-room design: charge limits, ventilation, leak detection, and ignition-source control for A2L and A3 fluids. Ammonia systems demand ventilation, detection, and relief to a safe location; carbon dioxide systems demand pressure relief and hypoxia protection because CO2 pools at floor level.
Blends introduce glide â the temperature difference between bubble and dew points â so zeotropic mixtures must be charged as liquid, and expansion devices are sized for the blend's glide. Pure-refrigerant practices (measuring superheat at a single point, for example) can mislead on a glide of several kelvin.
What the rules mean for a designer
- Montreal Protocol â phase down of ozone-depleting and HCFC substances, which removed R-22 and R-502 from new equipment in developed markets.
- Kigali Amendment â staged HFC reductions, so a new high-GWP choice may face service restrictions within the equipment's lifetime.
- F-gas style leak checking â large charges demand scheduled surveys, recorded repair, and leak-detection equipment rather than annual guesswork.
- Safety classification â ISO 5149 and ASHRAE 15 set charge limits, ventilation, and ignition control for A2L and A3 fluids.
- Machinery room design â refrigerant detection, relief piping to a safe discharge, and emergency ventilation for ammonia and large HFC charges.
- End of life â recovery, not venting, with recovery equipment and cylinder handling as part of the maintenance contract.
TEWI (total equivalent warming impact) is the honest metric: direct refrigerant losses multiplied by GWP plus indirect emissions from the energy the system consumes. A system with slightly higher GWP but materially better efficiency can win on TEWI; a leaky system with a very low-GWP fluid can still lose.
Cooling Loads: Sensible, Latent, and Peak
Cooling load is the sum of heat and moisture flows that must be removed to hold the space at its design condition. Sensible load changes temperature; latent load changes moisture. The two are kept separate because they are handled differently: sensible heat can be met by dry cooling, while latent load requires the air to be brought below its dew point on a coil or handled by a dedicated dehumidifier.
Envelope conduction follows , with from the assembly (0.2 to 0.4 W/m squared kelvin for insulated walls, 1.5 to 3.0 for single glazing) and from design conditions. Solar gain through glass depends on orientation, shading, glazing properties (SHGC), and frame fraction â on a west facade in the afternoon it often dominates the entire opaque envelope. Internal loads add people (roughly 120 W sensible and 100 W latent per person for office activity), lighting power density (ASHRAE 90.1 limits new office design to about 8 W/m squared), and equipment measured in watts per square metre.
Ventilation and infiltration carry both sensible and latent energy and are frequently the largest single load in humid climates. The latent load from outdoor air is
with humidity ratio in kilograms of water per kilogram of dry air and latent heat of vaporisation near 2450 kJ/kg at room temperature.
Peak sizing must never be done by adding every zone maximum together. The diversity factor reflects the probability that all loads peak simultaneously: a typical office block runs at 0.7 to 0.85 of the sum of zone peaks at the plant. Oversized equipment short-cycles, which wrecks dehumidification (the coil does not run long enough to reach dew point), wastes part-load efficiency, and costs more.
How a load calculation is built, in order
- Fix the outdoor design condition for the location and the indoor design condition for the space.
- Envelope conduction: area times U-value times design temperature difference for every opaque assembly.
- Solar gain: orientation, shading, glazing SHGC, frame fraction, and whether interior blinds are credited.
- Internal sensible gains: occupancy schedule, lighting power density, and equipment density.
- Infiltration: envelope leakage or air-change rate driven by stack and wind, or the minimum outside-air rate.
- Ventilation: code minimum outdoor air with both sensible and latent terms at the outdoor design condition.
- Add zone loads, apply the diversity factor, then select equipment with staging that matches the load profile.
- Sanity-check the result against a benchmark (watts per square metre or tonnes per square metre) before release.
Worked Example 2 â Room Load and Sensible Heat Factor
An office is 10 m by 8 m with a 3 m ceiling, 90 m squared of opaque envelope at W/m squared kelvin, 20 m squared of glazing with SHGC 0.40 facing 500 W/m squared irradiance, 12 occupants at 120 W sensible and 100 W latent each, 10 W/m squared lighting on 80 m squared floor, 1500 W of equipment, 0.5 air changes per hour infiltration, and 120 L/s of outdoor air at 28 degrees Celsius and 60 percent relative humidity into space at 23 degrees Celsius and 50 percent.
- Opaque conduction: W.
- Solar gain: W.
- Infiltration sensible: m cubed per second, giving W.
- Occupants sensible: W; lighting 800 W; equipment 1500 W.
- Total sensible: W, about 8.65 kW.
- Ventilation latent: outdoor humidity ratio kg/kg, indoor kg/kg; with kg/s, kW.
- Occupant latent: W. Total latent: kW.
- Total block load: kW, about 11.8 kW, and the sensible heat factor is .
Final answer: 8.65 kW sensible, 3.14 kW latent, 11.8 kW total, SHF 0.73.
The SHF fixes the coil selection and the supply air condition: the coil must produce air cool enough and dry enough that its own sensible heat ratio matches the room requirement, which is found by drawing the room ratio line from the room condition on a psychrometric chart toward the apparatus dew point.
The load arithmetic is repetitive enough to script, which also makes the assumptions visible:
import math
P_ATM = 101.3 # kPa
def p_sat(t_c):
"""Antoine-style saturation pressure of water, kPa (0 to 50 C range)."""
return 0.61094 * math.exp(17.625 * t_c / (t_c + 243.04))
def humidity_ratio(t_c, rh):
"""W in kg water per kg dry air from dry bulb and relative humidity."""
pv = rh * p_sat(t_c)
return 0.622 * pv / (P_ATM - pv)
# --- psychrometrics for the office in Worked Example 2 ---
Wo = round(humidity_ratio(28.0, 0.60), 4)
Wi = round(humidity_ratio(23.0, 0.50), 4)
m_dot = 0.120 * 1.20 # 120 L/s of outdoor air, kg/s
q_lat = m_dot * (Wo - Wi) * 2450.0 # kJ/kg latent heat
print(f"outdoor W = {Wo:.4f}, indoor W = {Wi:.4f}")
print(f"ventilation latent load = {q_lat:.2f} kW")
# --- sensible block load ---
q_envelope = 0.4 * 90 * (35 - 23) / 1000 # kW
q_solar = 20 * 0.40 * 500 / 1000 # kW
q_inf = 1.2 * (0.5 * 240 / 3600) * 12 # kJ/(m^3 K) x m^3/s x K
q_people = 12 * 120 / 1000
q_lights = 10 * 80 / 1000
q_equip = 1500 / 1000
q_sen = q_envelope + q_solar + q_inf + q_people + q_lights + q_equip
q_lat += 12 * 100 / 1000
print(f"sensible = {q_sen:.2f} kW, latent = {q_lat:.2f} kW, "
f"total = {q_sen + q_lat:.2f} kW, SHF = {q_sen / (q_sen + q_lat):.2f}")
# --- fan affinity laws: cost of throttling versus slowing down ---
for frac in (1.0, 0.8, 0.7, 0.5):
print(f"speed {frac:4.0%} -> flow {frac:4.0%}, "
f"power {frac ** 3:6.1%} of rated")
Running it reproduces the design numbers (8.65 kW sensible, 3.14 kW latent, SHF 0.73) and shows why a damper that holds flow at 70 percent while the fan runs at full speed wastes so much energy: at 70 percent speed the fan would draw only 34 percent of rated power.
Psychrometrics and Air-Side Systems
Psychrometrics is the arithmetic of moist air. Humidity ratio follows from vapour pressure:
where is total pressure and is partial pressure of water vapour (relative humidity times saturation pressure at the dry-bulb temperature). Enthalpy of moist air is approximately in kJ per kilogram of dry air. The four processes an air system performs â cooling with dehumidification, reheating, humidification, and mixing â are just lines on the chart with an energy and moisture balance at each node.
Coil performance is described by apparatus dew point and bypass factor: the fraction of air that passes the coil without being touched by the fin surface. A coil with bypass factor 0.2 leaves air at 80 percent of the way from entering condition to ADP, so surface area, row count, and face velocity all trade against each other. More rows and lower face velocity give a lower ADP and better dehumidification at the cost of pressure drop.
Psychrometric processes at a glance
| Process | Chart signature | Energy effect | Where it appears |
|---|---|---|---|
| Cooling and dehumidifying | Line down and left to the ADP | Sensible plus latent removal | Main cooling coil |
| Sensible cooling | Horizontal line left at constant W | Sensible removal only | Dry cooling coil, run-around loop |
| Reheat | Horizontal line right after cooling | Adds sensible heat back | Humidity control at low load |
| Adiabatic humidifying | Line up along constant enthalpy | Adds moisture, no net heat | Spray humidifier, evaporative pre-cool |
| Steam humidifying | Line up and right | Adds moisture and heat | Winter humidity control |
| Mixing | Point on the line between the two streams | Weighted average of both | Return and outdoor air mixing box |
| Fan and coil heat gain | Line right | Adds sensible heat to supply air | Fan energy and reheat coils |
Duct systems are sized by one of three methods: constant friction (equal pressure loss per metre, simplest, oldest), static regain (restores static pressure after each branch, best for large variable-air-volume systems), or velocity reduction. Typical friction rates sit near 0.8 to 1.2 Pa per metre of duct, and velocities are set by noise criteria â 3 to 5 m/s near quiet offices, up to 10 to 12 m/s where a silencer or lining can tolerate it. Filters are rated by MERV (ASHRAE 52.2): MERV 8 for prefiltering, MERV 13 or better where indoor air quality or equipment protection demands it, with pressure drop rising as loading increases â which is why filter differential pressure is a maintenance trigger. The fans and pumps behind those pressure losses are treated in Pumps and Turbines.
| Component | Function | Primary efficiency lever |
|---|---|---|
| Compressor | Raises refrigerant pressure | Staging, variable speed, lift reduction |
| Condenser | Rejects heat to ambient or water | Clean surface, low approach, correct flow |
| Evaporator | Absorbs heat from space or water | Airflow, approach temperature, superheat control |
| Expansion device | Meters liquid refrigerant | Properly sized valve, stable superheat |
| Fan and pump | Distribute energy | Variable speed drive, system-curve trim |
| Cooling tower | Heat rejection to atmosphere | Approach temperature, basin water treatment |
| Duct and pipe | Deliver energy | Low pressure drop, balanced branches |
| Controls | Sequences everything | Schedules, reset, economizer changeover |
Water-Side Systems: Chillers, Pumps, Boilers, and Towers
Large buildings use chilled water because water carries about 3500 times the energy of air per unit volume, so the distribution equipment is smaller and the terminal units can be compact. A centrifugal chiller suits large capacity with low evaporating-to-condensing lift, screw machines cover the middle range with good part-load behaviour, and scroll or reciprocating machines are staged in small increments. Air-cooled packages eliminate the tower but pay higher condensing temperatures; water-cooled machines reject at lower sink temperature and usually win on energy where a tower can be maintained.
Chiller efficiency is quoted in kW per ton or as COP, with part-load performance captured by IPLV (integrated part-load value) under AHRI 550/590 â a single number weighted across the operating hours of a typical year. A machine with excellent full-load numbers and poor 40 percent performance can cost far more to run than a slightly less efficient competitor, which is why IPLV matters more than nameplate. The condenser and evaporator duties on either side of it are heat-exchange design problems in their own right, covered in Heat Transfer.
Choosing a machine type
| Machine | Capacity range | Full-load efficiency | Part-load behaviour | Typical duty |
|---|---|---|---|---|
| Centrifugal | 300 to 3000 kW | Best at large capacity | Good with VFD and vanes | District and large campus plants |
| Twin screw | 150 to 1000 kW | Very good | Strong with slide-valve staging | Mid-size commercial |
| Scroll | 30 to 400 kW | Good | Staged by cylinder or unit count | Small commercial and modular |
| Reciprocating | 20 to 300 kW | Moderate | Cylinder unloading | Legacy and specialist duties |
| Air-cooled package | 50 to 1200 kW | Lower (higher sink) | Staged compressors | Sites without tower or water |
| Absorption and heat recovery | 100 to 5000 kW | Runs on heat, not work | Limited turn-down | CHP and waste-heat plants |
Hydronic distribution has its own physics. Pump power follows the affinity laws (, so halving flow at double the head saves little, while slowing the pump saves the cube of speed), pipe sizing balances velocity (1 to 2.5 m/s in buildings for noise and erosion) against pressure drop, and every valve that throttles a pump at full speed converts electricity into hot water. Primary-secondary or variable-primary arrangements decouple flow control from chiller protection, and hydraulic separators prevent the pumps from fighting each other.
Towers are rated by approach â the gap between leaving water and ambient wet-bulb â and range (entering minus leaving water). A 5 kelvin approach on a 26 degree Celsius wet bulb gives 31 degree Celsius condenser water, which sets the chiller's head. Approach degrades with fouling, biological growth, and scale, so water treatment and verification of approach temperature are direct energy measures.
Heating side mirrors the cooling logic: boilers are rated by combustion and seasonal efficiency, with the biggest real losses being latent heat up the flue (gas-fired condensing units reach 90 to 97 percent by recovering it, while non-condensing units top out near 82 to 88 percent) and standby losses. Hydronic heating coils and radiators are selected on the same apparatus-dew-point logic as cooling coils, with water temperature reset as the primary part-load strategy.
Part-Load Control, Commissioning, and Maintenance
Part load is where systems earn or waste their operating budget. Fans and pumps follow the affinity laws:
so reducing fan speed to 70 percent delivers 70 percent of the flow at 49 percent of the pressure and 34 percent of the power. Any system that instead throttles a damper or valve while running the machine at full speed pays the difference as noise, heat, and wear.
Sequences of operation define how the plant actually behaves: cooling setpoints, chilled water reset based on supply pressure or valve position, condenser water reset based on load, staging rules with minimum run times, economizer changeover by enthalpy or by dry bulb with humidity limits, and alarm limits on discharge pressure, superheat, and vibration. An air-side economizer is valuable whenever outdoor air can meet the load without mechanical cooling and with acceptable humidity â much of the year in dry climates and in shoulder seasons nearly everywhere.
Commissioning tests worth scheduling
- Calibrate every temperature, humidity, and CO2 sensor against a reference before any sequence is judged.
- Prove each control sequence at the controller, then again end to end at the equipment.
- Measure and balance air and water flow, not just valve position or damper command.
- Verify fan and pump speed against the system curve after balancing.
- Run the plant at low load and confirm that staging and reset behave without hunting.
- Check economizer changeover with a controlled outdoor condition, including the humidity limit.
- Trend superheat, subcooling, and condenser approach for a week to confirm charge and cleanliness.
- Repeat the functional tests after any control change, and file the results with the design intent.
Commissioning verifies that the installed system meets design intent under real weather and occupancy: functional performance tests of each sequence, calibration of temperature, humidity, and CO2 sensors, airflow and water flow verification, and a seasonal performance test. ASHRAE Guideline 0 defines the process and ASHRAE Guideline 1.1 covers HVAC systems; ASHRAE 90.1 sets the energy floor, and ASHRAE 62.1 sets the ventilation floor that no efficiency measure is allowed to undercut.
Maintenance keeps the numbers where the design put them: coil cleaning (a fouled condenser raises lift directly), filter changes triggered by differential pressure rather than by calendar alone, refrigerant charge verification by superheat and subcooling (both low charge and overcharge hurt), non-condensable checks on water-cooled machines, belt and pulley inspection, vibration trending on compressors and fans, and leak detection surveys on large charges.
đĄLift Is the Whole Efficiency Story
â ī¸Oversizing Is Not a Safety Margin
Common Mistakes
Ignoring the ventilation and infiltration load
Fix: Fresh air latent load can dominate in humid climates; take outdoor air requirements from ASHRAE 62.1 and add energy recovery where the enthalpy difference is large.
Oversizing from a worst-case guess
Fix: Short cycling kills dehumidification and part-load efficiency; size from a calculated peak with diversity and provide staging instead.
Throttling instead of slowing down
Fix: Dampers and valves at full fan or pump speed convert electricity into heat; fit variable-speed drives where the system spends most of its hours below design flow.
Skipping filtration and coil maintenance
Fix: Dirty filters raise fan energy and starve airflow, while fouled condensers widen lift; schedule both from differential pressure and approach temperature readings.
Key Takeaways
- COP equals cooling effect over compressor work, and both are read straight off the enthalpy diagram.
- Carnot COP and second-law efficiency tell you how much of the theoretical performance the machine is leaving on the table.
- Loads split into sensible and latent parts, and the sensible heat factor fixes coil selection and supply air conditions.
- Peak equipment size comes from calculated load with diversity, not from adding zone maxima.
- Part-load control, not nameplate efficiency, determines annual energy cost â fan and pump power follows the cube of speed.
- Commissioning and scheduled maintenance are what keep design performance alive in the field.
Frequently Asked Questions
What is superheat and why does it matter?
Superheat is the temperature rise of suction vapour above its saturation temperature at the evaporator pressure. Enough of it (typically 5 to 8 kelvin) guarantees that no liquid reaches the compressor, protecting valves, scrolls, and lubricant return; too much superheat means the evaporator is being starved of refrigerant, so capacity falls and discharge temperature rises.
Why does a higher condensing temperature destroy COP?
Raising condensing temperature raises the compressor discharge pressure for the same cooling effect, so the compressor does more work per kilogram circulated. The same effect appears from the other side when the evaporating temperature drops â both widen the lift between the two reservoirs.
When is an air-side economizer worth installing?
Whenever outdoor air at acceptable humidity and filtration can offset the mechanical cooling load for a meaningful number of hours. Economizer changeover is normally controlled by enthalpy comparison or by dry bulb with a humidity limit, and the annual savings usually justify the damper and control additions in all but the most humid climates.
How do you check that a chiller is charged correctly?
Measure superheat at the evaporator outlet and subcooling at the condenser outlet and compare them with the manufacturer's charge charts at the current operating condition; low subcooling usually indicates undercharge or a flooded condenser, while high discharge pressure with normal subcooling points to non-condensables or a fouled condenser. Trending both over time reveals slow leaks long before a trip occurs.
Interview Questions
Q1: A chiller shows low capacity and high amps. What is your diagnosis sequence?
Check refrigerant charge through subcooling and superheat first, then condenser fouling and non-condensables (high head pressure with normal subcooling), then airflow or water flow across the evaporator, expansion valve metering and superheat control, and finally a refrigerant mix-up from a previous repair. Each of those shows a distinct signature in the four pressures and temperatures.
Q2: How would you cut HVAC energy in an existing building?
Start with a baseline from utility data, then fix schedules and setpoints, clean coils and filters, verify charge, add variable-speed drives where dampers or valves throttle, seal duct leakage, recover exhaust-air energy where the enthalpy difference justifies it, and reset chilled water and supply air temperatures from valve position. Re-measure and trend to prove each step.
Q3: Explain how you would size the cooling plant for a new office floor.
Build the envelope load from U-values and design deltas, add solar by orientation and shading, internal gains from occupancy, lighting power density and equipment density, then ventilation from ASHRAE 62.1 with the outdoor design condition for both sensible and latent. Sum zone peaks with a diversity factor for the block load, round to available machine sizes, and confirm that staged capacity covers the low-load hours without short cycling.
Q4: What is the difference between sensible heat factor and SHR of the coil?
Both are ratios of sensible to total heat, but the room SHR describes the load the space must shed, while the coil SHR describes what the coil removes. The coil must be selected so that its apparatus dew point and bypass factor deliver a supply air condition whose line through the room condition matches the room SHR, otherwise humidity drifts even when temperature holds.