Heat Pump Cycles and Performance Metrics

Thermodynamics & Heat TransferPower and Refrigeration CyclesđŸŸĸ Free Lesson

Heat Pump Cycles and Performance Metrics

What You'll Learn

  • 1Describe the heating mode of a vapor compression unit
  • 2Compute heating COP and its Carnot ceiling
  • 3Compare air, ground, and water source systems
  • 4Select seasonal metrics and backup strategy

A heat pump runs the same compressor, condenser, evaporator, and expansion device as an air conditioner, only in the other direction, and that single fact explains most of its economics. Delivering heat with a machine that moves it instead of burning fuel or resistance heating can return three to five units of heat for each unit of electricity. The catch is that performance depends on temperature lift, which worsens exactly when the weather turns coldest. This lesson covers heating COP, Carnot ceilings, seasonal ratings, source selection, and backup design, with numbers you can check by hand.

Theory and Foundations

Heating Mode and the COP Definitions

In heating mode the outdoor coil absorbs heat from air, ground, or water, and the indoor coil rejects that heat plus the compressor work into the space. The first law for the machine is a simple addition:

Because delivered heat always exceeds absorbed heat by exactly the work input, heating COP is bounded below by one and rises as machinery improves:

For the same reservoirs the two are locked together, . A unit absorbing outdoors while consuming of work delivers indoors, a heating COP of 4, and the corresponding cooling COP is 3. In practice the compressor delivers the duty through enthalpy rise, so the same numbers come from the hardware as across the condenser and across the compressor.

Carnot Limits and Temperature Lift

The reversible heating COP equals the delivery temperature divided by the temperature lift, both on an absolute scale:

Heating a house to () while the outdoors sits at () gives a lift of and a Carnot ceiling of . Real machines reach a fraction of that because of finite approach temperatures in the coils, compressor irreversibility, throttling loss, and frost, with field values near 3.5 to 4.5 in mild weather. The gap matters: at that operating point a unit at COP 3.5 sits at percent of the reversible ceiling, so most of the loss is internal irreversibility rather than poor heat exchangers.

Two bounds keep the number honest. Because , the heating COP is always at least 1 even for a machine that converts every joule of work into delivered heat, so any measured value below 1 means the metering or the definition is wrong. At the other end, as the outdoor temperature rises toward the delivery temperature the lift approaches zero and the ceiling grows without bound, which is why mild days are cheap to heat. As the weather turns cold the lift approaches the delivery temperature itself and the ceiling falls toward 1, where the heat pump barely outperforms the resistance heater it was installed to avoid. Field capacity follows the same curve, giving up roughly 1 percent for each kelvin the outdoor coil drops below its rating point while the building demand climbs.

Seasonal performance follows the same energy accounting summed over the year:

HSPF is the same quantity in Btu per watt hour, and multiplying SCOP by 3.412 converts between them directly.

Air, Ground, and Water Sources

Air source units are simplest and cheapest, but outdoor air gets cold exactly when heating demand peaks, so capacity and COP both sag while defrost cycles add losses of 5 to 10 percent in cold humid weather. Ground loops hold near to year round, which keeps the lift short and stable. Water source units behave similarly where a pond or well exists.

Capacity must satisfy the building balance point, the outdoor temperature where available capacity equals building heat loss:

Below that temperature the gap is carried by supplemental electric resistance, whose COP is exactly 1. Because heat pump capacity falls as ambient temperature drops while building load rises, the balance point is typically between and , and sizing against design day rather than average winter keeps backup runs rare rather than routine.

Key Formulas

Worked Examples

MetricBasisTypical value
Heating COPinstantaneous rating3 to 5 air source
Carnot heating COPtemperature limits only10 to 18 in mild weather
HSPFseasonal Btu per watt hour8 to 12 for cold climates
SCOPseasonal average COP3 to 4.5 in mild climates
Balance pointcapacity against building load0 to -10 C typical
Defrost penaltycapacity and energy loss5 to 10 percent cold humid

Real-World Examples

  • Mild winter operation - Heating to from gives a Carnot ceiling near 18.4 and a real COP near 4, which is why most hours of the season run efficiently.
  • Ground loop stability - A loop near holds lift near , keeping COP above 4 through January where air source drops below 3.
  • Backup heat cost - Below the balance point, of resistance strips costs of electricity instead of the a COP 3 unit needs, tripling the demand charge for those hours.
  • Annual fuel savings - Delivering of heat at COP 3.2 costs instead of with resistance, a saving of 8250 kWh every winter.

💡Capacity Falls When You Need It Most

Outdoor temperature drop raises lift and triggers defrost, so output and COP decline exactly as load grows. Size against the design day, not the average, and set the balance point so backup only carries the deepest cold.

Common Mistakes

Sizing on average winter load

Fix: Size against design day heat loss at the local heating design temperature.

Using cooling ratings for heating

Fix: SEER describes cooling; heating needs COP, HSPF, or SCOP for the same season.

Ignoring defrost penalties

Fix: Reverse cycle defrost cuts capacity in cold humid weather, so include it in seasonal performance.

Key Takeaways

  • Heating output equals evaporator heat plus compressor work, so q H equals q L plus w.
  • Heating COP is exactly one higher than cooling COP at the same limits: COP H equals COP R plus 1.
  • Ground and water sources stabilize lift and avoid defrost penalties, holding COP above 4 in deep winter.
  • Balance point and seasonal metrics, SCOP and HSPF, govern real operating cost rather than nameplate COP.

Frequently Asked Questions

Does a heat pump work below freezing?

Yes, but capacity and COP fall as lift grows, and frost on the coil adds defrost losses. At outdoors the Carnot ceiling for delivery is only , less than half its mild weather value.

What is the balance point?

It is the outdoor temperature where heat pump capacity equals building heat loss, below which backup heat must run. Setting it requires matching the capacity curve against the load line, and a poorly chosen point either wastes resistance energy or leaves the house short.

When is resistance heating acceptable?

As short term backup and for small loads. Running it as the main source wastes two thirds of the energy, since its COP is 1 while even a modest heat pump holds 2.5 to 3.5 through most of the season.

Interview Questions

Q1: Why is heating COP always higher than cooling COP?

Heating output includes evaporator heat plus compressor work, so it exceeds cooling COP by exactly one at identical temperature limits.

Q2: How do you choose between air and ground source?

Compare loop cost with seasonal lift; ground source wins where winters are long and cold, since a 10 C loop keeps lift near 11 K while outdoor air swings to minus 20 C.

CW

ChatWhole Learn Editorial Team

Written by experienced data scientists, software engineers, and educators. All content is reviewed by industry professionals to ensure accuracy and relevance.

Last reviewed: 2026-09-27

—
☆☆☆☆☆
0 ratings

Rate & Feedback

Related Tutorials

Content with similar topics across other courses

Need Expert Thermodynamics & Heat Transfer Help?

Get personalized tutoring, project support, or professional consulting.

Advertisement